910Telecom customers receive reliable, high-quality electrical power with multiple incoming commercial grids as well as generator and battery back-up. Denver’s central location within the US offers low risk of service interruptions due to natural disasters.
There are nine 1,000-kva transformers providing 27,758 amps at 208 volt 3-phase 4-wire.
DC power (48-volt) is available with “true” A & B configuration. Tenant spaces have their own DC power plants.
Four 2-Megawatt auto-start back-up generators on the roof are fueled from dedicated tanks with sufficient fuel (4,000 gallons per tank) to keep the system operating for up to 72 hours. Generators kick on within 5-15 seconds in case of power failure. Monthly tests ensure that the system is ready and functions as intended.
Additionally, the entire building is designed with fire suppression, HVAC, and security in mind:
- A pre-action double interlock waterless fire suppression (FM-200) system is installed in most of the spaces.
- The building has no central air conditioning or ventilation system. A majority of tenants have their own closed-loop air conditioning system located on the rooftop. Some also have chilled water supplied by Xcel Energy.
- The building is secured with a monitored card access system. Badges allow 24/7/365 access. Building security cameras are installed in all elevators and hallway floors. A security guard is stationed at the main floor entry desk weekdays.
Plus, 910Telecom installs fiber optic cable and copper cabling within EMT conduit between floors and suites to protect your services from any interruption.